Can MDGF be combined with ZSI?
Issue:
ZSI on MDGF systems

Product Line:
Circuit breakers

Resolution:
On MDGF systems:
  • In a Main-Tie-Main system, the main breaker cannot be short time ZSI restrained by the tie breaker.
  • Since the main circuit breaker cannot be restrained on short time, it must be ZSI self restrained on the short time function.
  • The main circuit breaker can be ground fault restrained by the feeder breakers.
  • Installation of GF ZSI has no effect on MDGF and MDGF has no effect on GF ZSI.