Video: How Do I Configure an ATV320 Drive for 2-Wire Control?

Resolution:



Follow these steps to configure the drive for 2-wire control:

  1. From the main menu, navigate to: CONF → FULL → I/O (I_O-)
  2. Locate the TCC parameter.
  3. Set TCC = 2C to enable 2-wire control.

Selecting the 2-Wire Control Type

After enabling 2-wire control, choose the desired operating mode using the TCT parameter:

  • TRN (Transition Mode) - Default setting
  • LEL (Level Mode)

Operating Modes

Transition Mode (TRN)

  • The drive must be powered on before a run command is issued.
  • A transition of the run signal is required to start the drive.
  • Recommended for most applications.

Level Mode (LEL)

  • The run command can remain active while the drive is powered off.
  • When power is restored, the drive will start automatically if the run command is present.
  • If no run command is present, the drive will remain in RDY (Ready) status until a run command is received.

Warning: Level Mode (LEL) may cause the drive to start automatically after a power cycle. Ensure this behavior is safe and appropriate for your application before enabling it.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings