How do I setup Level Control on an Altivar 600 Process Drive?
Resolution:
The Level Control function in the Altivar 600 Process Drive is designed for water and wastewater applications that require automatic tank filling or emptying using pumps.
This feature helps prevent:
- Tank overflow during filling operations
- Complete tank emptying during drain or pumping operations
The Level Control function can:
- Control the speed of one Variable Speed Pump (VSP)
- Automatically stage and de-stage up to five additional pumps on ATV600 drives
- Support Fixed Speed Pumps (FSPs) or additional Variable Speed Pumps (VSPs) in multi-pump applications
Multi-Drive Configuration Requirements
For multi-drive pump control applications, the following are required:
- Altivar 600 firmware version 1.6 or later
- VW3A3721 Multi-Drive Ethernet Communication Card
- Standard Ethernet cables
- Fixed IP address configuration for all connected drives
The Multi-Drive feature enables coordinated operation of multiple drives in Multi-Pump mode.
Additional Information
- Step-by-step configuration instructions are available in the attached setup document.
- The Level Control function is available only on Altivar 600 series drives.
- This feature is not supported on Altivar 900 series drives.
- Multi-drive applications require the VW3A3721 Multi-Drive Communication Card.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)