Do we have temperature deratings for the TeSys U starters?
Issue:
What are the temperature deratings for the LUB starters?
Product Line:
Operating Mechanism and Disconnect Switches
Environment:
North American Products
Cause:
Would like to use the TeSys U above or below rated temperatures
Resolution:
We can commit only on the ambient temperature for operation and storage written in the catalogue.
The limitation is due to the use of electronic components in control unit, as exemple maximum ambient temperature is different between LUCM (+60°C) or advanced control unit (+70°C).
Outside of the -25°C to +70°C range, we can not have a derating as the control unit may not operate properly and could be in internal fault.
Released for: Schneider Electric Canada