How To configure a different Modbus address to each serial COM Port in the SCADAPack SLAVE Device ?

Issue

Assigning Different Modbus Addresses for each COM Port in the Slave SCADAPack

Product Line

SCADAPack E RTU

Environment

Windows OSes, E Configurator

Resolution

The Resolution Provides detailed steps in E Configurator Software to assign different Modbus addresses to COM Ports in SACADAPACK 535E


1- Install E Configurator 8.12.5
2- Update the SP535E to latest Firmware Version 8.12.5
3- In the Port 0-3 page in case of 300E Series or Port 0-4 in case of 500E Series, Configure The Serial Ports with the Modbus settings to be matched with the Modbus Master, an example is below
E Configurator

4- In the Point Browser page, Add 5 Analog System Points to be configured
Where:

ports
AddressDescription
52014System Point
52017Port 1 Modbus Address
52018Port 2 Modbus Address
52019Port 3 Modbus Address
52020Port 4 Modbus Address

E Configurator

5- Write the Following Values to assign different Modbus Addresses to Port 1 & Port 2

ports
Port AddressValue
520140
52017 (Port 1)1
52017 (Port 2)2

warning
warningIf a valid number in the range of 1 - 247 (according to Modbus Specifications https://wingpath.co.uk/docs/PI_MBUS_300.pdf) has been assigned to system point "52014", SCADAPack RTU will be configured with the same one Modbus address accross the all serial ports according to the value in "52014" and Values of "52016-52020" will be set to the same value of "52014"
warning
warningIf "Zero" has been assigned to "52014", User can configure different Modbus addresses for each COM Port

6- Press Write Button
E Configurator

7- Perform the Power Cycle the SCADAPack
8- Use Read to check if the new addresses were applied
E Configurator

9- Configure the Modbus Master Address with Value 1 and Connect the Serial Cable between The Modbus Master device and Port 1 of SCADAPack Slave Device.
10- Check that the Communication is good when Tx &Rx LEDs of COM1 are blinking.
11- Move the Serial Cable to Port 2; The Communication will be lost until you change the Modbus Master address to Value 2

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings