Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Does Schneider offer DC rated Panelboards?

Article available in these languages: Spanish

Issue:
Panelboard for DC rated applications

Product Line:
NQ NF I-Line Panelboards

Environment:
Products sold in North America

Resolution:
Only the NQ and I-line panels are rated for DC, due to the DC rated breakers that can be installed in them.
NQ panels use QO/QOB breakers which are rated up to 48VDC.  I-Line breakers can be rated up to 250VDC max.
For DC applications using I-Line Panelboards, the amperage range availability is small, 15A-250A maximum using Powerpact H and J frame breakers .