Does a 5.0P or 5.0H trip unit have a ground fault alarm indicator on the LED display screen?
Issue:
Is there a ground fault alarm indicator on the trip unit itself?
Product Line:
Circuit breakers
Environment:
Micrologic 5.0P and 5.0H trip units
Resolution:
No, there is not an indicator on the trip unit itself. Also, the trip unit LCD screen gives no indication when the ground-fault pickup has been reached. The GF alarm can only be indicated by:
1) sending the signal through the M2C or M6C contact block, or
2) reading the GF alarm through Modbus Register if available. See FA306313 for more information on reading ground-fault alarm through Modbus.
3) trip unit alarm history (wrench button, go to history logs, then scroll to alarm history)
Is there a ground fault alarm indicator on the trip unit itself?
Product Line:
Circuit breakers
Environment:
Micrologic 5.0P and 5.0H trip units
Resolution:
No, there is not an indicator on the trip unit itself. Also, the trip unit LCD screen gives no indication when the ground-fault pickup has been reached. The GF alarm can only be indicated by:
1) sending the signal through the M2C or M6C contact block, or
2) reading the GF alarm through Modbus Register if available. See FA306313 for more information on reading ground-fault alarm through Modbus.
3) trip unit alarm history (wrench button, go to history logs, then scroll to alarm history)
Released for: Schneider Electric Canada


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.