How to resolve a stop checkback fault on the TeSys T
Issue:
Why does the TeSys T have a stop checkback fault any time an attempt is made to run the motor?

Product Line:
Tesys T Motor Management Systems

Environment:
Tesys T products

Cause:
Programming and Troubleshooting

Resolution:
The stop checkback fault occurs when the motor starts to run without the TeSys T issuing a run command.
This most frequently occurs when the TeSys T is set to independent operating mode but the local operators are wired directly to the contactor, instead of the LTMR block.
If this is causing the issue it can be resolved by changing your operating mode from 2 or 3 wire independent mode over to 2 or 3 wire overload mode.
If the local controls are wired to your TeSys T block you may need to look at what else could be starting your motor.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Register Your Product
  • Blog
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings