{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
How to correct error 22321 Liquid:Calculation of Density at base conditions unsuccessful in Realflo?
Scenario:
  • The scadapack is polling values from the Coriolis Meter.
  • When the Coriolis Meter losses connections or it stop communicating, The Realflo Run liquid will use the default setting parameters.
  • Make sure that correct parameters are entered on the Default value.
For example: If the default value for the Density was set to 1 when measuring Liquid and the Coriolis meter losses communications then
the flow computer will used the default value 1 to calculate the flow and will give an error result of 22321 "Liquid:Calculation of Density at base conditions unsuccessful"

Use the table below for Density default value:

Schneider Electric Canada

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: