Can you fine tune the trip settings of Powerpact H, J and L frame breakers?

Issue:
Can you adjust the Micrologic trip unit of electronic H, J and L frame breakers in 1 A increments?

Product line:
Molded case circuit breakers

Environment:
Powerpact H, J and L frame breakers with Micrologic trip units

Resolution:
You must have the Micrologic ammeter 5.2A/6.2A or energy 5.2E/6.2E trip unit in order to fine tune the settings.  The keypad can be used to make fine adjustments in 1 A steps below the maximum value defined by the setting on the dial.

See the attached document for instructions from our Micrologic trip unit bulletin 48940-312-01 for a step-by-step guide on making these settings.

Schneider Electric Canada

Attachment(s)
Fine Tuning Micrologic Settings.pdf [56.88 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings