Is it possible to fit 42 EDB14020EPDBA breakers in a 400A Main Lug Only NF panel, 480/277V 3Ph 4W ?

Issue:
How many EDB14020EPDBA breakers will mount into a 400A Main Lug Only NF panel, 480/277V 3Ph 4W ?

Product Line:
NF Panelboards

Environment:
Application

Cause:
Verification

Resolution:
The NF 84 circuit interior is actually two interiors bussed together.  The bussing goes between ckts 41-43 and 42-44, so a two pole breaker cannot mount in those locations.   Also, ckts 83 & 84 cannot accommodate a two pole breaker.