Is it possible to fit 42 EDB14020EPDBA breakers in a 400A Main Lug Only NF panel, 480/277V 3Ph 4W ?
Issue:
How many EDB14020EPDBA breakers will mount into a 400A Main Lug Only NF panel, 480/277V 3Ph 4W ?
Product Line:
NF Panelboards
Environment:
Application
Cause:
Verification
Resolution:
The NF 84 circuit interior is actually two interiors bussed together. The bussing goes between ckts 41-43 and 42-44, so a two pole breaker cannot mount in those locations. Also, ckts 83 & 84 cannot accommodate a two pole breaker.
How many EDB14020EPDBA breakers will mount into a 400A Main Lug Only NF panel, 480/277V 3Ph 4W ?
Product Line:
NF Panelboards
Environment:
Application
Cause:
Verification
Resolution:
The NF 84 circuit interior is actually two interiors bussed together. The bussing goes between ckts 41-43 and 42-44, so a two pole breaker cannot mount in those locations. Also, ckts 83 & 84 cannot accommodate a two pole breaker.
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.