Type 2 coordination is not possible with ATS22 due to the soft starter internal design of power semiconductor & its internal by-pass . Only table for coordination type 1 is available in the catalog. Attached pdf pages for type 1 coordination .
Released for: Schneider Electric Canada


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.