Test trip TeSys D LRD Overload relay

Issue:
How can the LR*D overload relays be test tripped?

Product Line:
IEC Contactors - GIC Product

Environment:
US Product

Cause:
Product Characteristics

Resolution:
There is a slot on the front of the device labeled "test" if you slide a small screw driver into this slot you can slide it across and trip the device. You should then see a small yellow flag and the overload contacts will be in the tripped state.