How can we help you today?

Why I have a popup error message “Operation unsuccessful” when I start the operation PC-to-Controller download with SoMachine-Basic V1.5 SP1 ?

Only with SoMachine-Basic V1.5 SP1, when trying to download an application from PC to M221 controller while the application is protected by a password, we may have a popup error message "Operation unsuccessful" and then another one "could not receive response from controller"  in case the option "Reset memories" is not checked.

In the Commissioning tab, when connected to the M221 PLC, check the download settings and activate the option Reset memories (see attached screenshot) in order to success to download.

Schneider Electric Canada

Attachment(s)
ResetMemories.jpg [110.02 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center