How to connect 4203DS analog input to sensor that has 0-20mA or 4-20mA current output?
4203DS transmitter has two voltage 0-5V analog inputs. To "convert" voltage analog inputs to current analog inputs install 250 Ohms resistor between terminal board connections labeled AIN0 or AIN1 and COM as shown on picture below.