Can a contactor installed between the VFD output and the motor be used to start and stop the motor while the VFD remains running?
Resolution:
No. Using a contactor between the VFD and motor for normal Start/Stop control is not recommended.
Opening or closing an output contactor while the VFD is actively supplying the motor can interrupt or reconnect the VFD's pulse-width modulated (PWM) output. This can cause improper operation and may potentially damage the VFD output stage or motor.
For normal operation:
- Use the VFD's Start/Stop commands to control the motor.
- Do not use an output contactor to routinely cycle the motor ON and OFF while the VFD is running.
- A contactor installed between the VFD and motor should be used for motor isolation or other applications specifically permitted by the drive documentation, rather than as the primary Start/Stop control.
- Always refer to the installation and programming documentation for the specific Altivar model when an output contactor is required.