Can I use an external +24VDC supply to trigger the logic inputs on an ATS22 S6 soft starter?

Resolution:

Yes, you can use an external +24 VDC power supply to trigger the logic inputs on an ATS22 S6 soft starter.

How to connect it correctly:

  1. Connect the +24 VDC from the external supply to the desired logic input.
  2. Connect the common (0V) of the external power supply to the common terminal on the ATS22.

Important:

  • The common connection is required for proper operation.
  • If the commons are not connected:
    • The soft starter may not start, or
    • It may operate unreliably.

Ensuring a shared common reference guarantees stable and consistent input signal detection.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)


Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings