What are the specifications for the STO inputs on the ATV Process drives?

Resolution:
Characteristics of ATV Process STO inputs
PLC compatibility:  complies with IEC/EN61131-2 logic type 1 and type 3, for voltage levels
Positive logic (Source):
State 0 if  ≤ 5Vdc or STO not wired,
State 1 if ≥ 11Vdc
Impedance: ≥ 2.2kΩ
Maximum current:      10mA min at 19V input for external (Preventa) Relay
Response time: 10ms

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.