Can the sub feed lug kit SL800M5 be change from accommodating (3) 3/0 - 500kcmill to (4) 3/0- 500 kcmil wire used with an ILine 800A MCB Panelboard ?

Issue:
Can the sub feed lug kit SL800M5 be change from accommodating (3) 3/0 - 500kcmill to (4) 3/0- 500 kcmil wire used with an ILine 800A MCB Panelboard ?

Product Line:
I Line Panelboard accessories

Environment:
Application

Cause:
Product Features

Resolution:
Due to the 800A rating of the sub feed lug kit , there is no provisions, or wire bending space for the SL800 , used with a HCM , or HCP interior to run (4) 500 kcmil/ phase .
Using a HCRU interior with back fed PG 1200AF/800AT breaker, or SL1200P5 Sub feed lug kit , will offer (4) 3/0-500 kcmil/phase

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings