TS_DIAGNOSTIC_FLAGS for the BMXERT1604T is reporting an 137 error.

Issue
TS_DIAGNOSTIC_FLAGS for the BMXERT1604T  is reporting an 137 error.

Product Line
BMXERT1604T

Environment
Unity, OFS


Resolution
Displaying the TS_DIAGNOSTIC_FLAGS  in bits.  137(binary 10001001 ) shows that the  buffer is being reported as full.

This works as designed and it is not a defect in the BMXERT1604T

The following conditions can cause the buffer to be reported as full.
  • If the OPC server is not able to read the 'BMXERT1604T' event in time, the buffer will be reported as  full.
  • If the OPC server or EFB read ERT event is slower than the ERT event generated . the group number which store the events in the ERT will exceed 255,
Note: When the 'Buffer Full' bit is set, any new events will not be recorded.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings