How can we help you today?

What is the dwell Setting / Time for Hi pot testing a V5D7133Y000A, 15kV/40kA (750MVA) vacuum circuit breaker?

Issue:
For testing a V5D7133Y000A breaker, what would be the time for Hi-pot test, and at what voltage?

Product Line:
VR Vacuum breaker

Environment:
Maintenance

Cause:
Testing

Resolution:
This a V5D7 VR breaker , 15kV/40kA ), (750MVA) ,  and should be Hi-Pot tested @ 36kV V(RMS) for a 1 minute Dwell / per phase.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings