What is the dwell Setting / Time for Hi pot testing a V5D7133Y000A, 15kV/40kA (750MVA) vacuum circuit breaker?
Issue:
For testing a V5D7133Y000A breaker, what would be the time for Hi-pot test, and at what voltage?
Product Line:
VR Vacuum breaker
Environment:
Maintenance
Cause:
Testing
Resolution:
This a V5D7 VR breaker , 15kV/40kA ), (750MVA) , and should be Hi-Pot tested @ 36kV V(RMS) for a 1 minute Dwell / per phase.
For testing a V5D7133Y000A breaker, what would be the time for Hi-pot test, and at what voltage?
Product Line:
VR Vacuum breaker
Environment:
Maintenance
Cause:
Testing
Resolution:
This a V5D7 VR breaker , 15kV/40kA ), (750MVA) , and should be Hi-Pot tested @ 36kV V(RMS) for a 1 minute Dwell / per phase.