Is there a way to test the SDE overcurrent trip switch on PowerPacT circuit breakers?

Issue:
How is the SDE tested in PowerPacT breakers?

Product Line:
Circuit Breakers

Resolution:
The SDE overcurrent trip switch contacts are activated ONLY when the Micrologic trip unit causes the breaker to trip from an overload, short circuit, or ground fault. Therefore, the function of the SDE can be tested by tripping the breaker with primary or secondary injection testing. The SDE cannot be tested by pressing the red trip button, nor can it be tested by tripping the breaker with a shunt trip or undervoltage trip accessory.

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings