How can we help you today?

Why ports are not available for selection inside E-configurator modbus master scanner or How to setup modbus master scanner with modbus slave device with scadapack RTU ?

Yes its observed that when ports 1 or port 2 is to be selected inside modbus scanner of e-configurator through "ADD DEVICE"  button  Port selection field is empty and Port 1 and Port 2 is not available for selection.
To make it appear assign Port 1 function field in 'Ports' to Modbus master ( Modbus RTU) in Ports configuration . Refer screen shot below.

modbus slave device with scadapack RTU

Later go to Modbus Scanner ---> Add Device ---> Select correct port like port 1 or port 2.

modbus slave device with scadapack RTU


Final step is to configure scanner line inside scanner table with all the information related to modbus protocol to make communication successful.

modbus slave device with scadapack RTU




Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings