Advantys DTM – Bad DDDT structure from Advantys with custom Labels in Unity Pro V13.

Goals and Symptoms

Operating with Unity Pro V13 with an application using TeSys and STB devices, after import of custom labels in Advantys, the DDDT structure is not correct.

Facts and changes

It is observed that Advantys is exporting the variables in different order than expected.
This wrong behaviour is related to Advantys DTM.

Causes and Fixes

As workaround follow the steps below with a ‘’fake’’ modification and build to recover normal situation.
Launch Advantys configuration software from the DTM browser and do a small modification by opening the module editor of any module in the Advantys island. Build the advantys configuration .

Revert the change you have done and rebuild the island again. Then the variables are properly aligned in Unity Pro.

bFO44476058

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings