How can we help you today?

Can We Use The GV2AF3 to Interconnect The Reversing LC2D Contactors And GV2 Manual Starter?

Issue:
GV2AF3 for interconnecting LC1D non-reversing contactor and a GV2 starter, will this also work with a reversing LC2D contactor?

Product Line:
TeSys™ GV Manual Starters and Protectors

Environment:
IEC Contactors and Starters

Resolution:
Yes. In addition, spacers should be placed under each of the contactors as shown ont he attachment in the non-reversing photo. Spacer part number is GV1F03.

Schneider Electric Canada

Attachment(s)
GV1F03 spacer.pdf [665.91 KB]