How can we help you today?

Do the PowerLogic and ION meters support low voltage DC power supplies?

Issue
Customer would like to determine available DC Low Voltage Supply options for a meter

Product line
PowerLogic Meter
ION Meter

Environment
Power Supply

Cause
Customer wants to determine available DC Low Voltage Supply options for a meter

Resolution
MeterSpecification
ION9000No DC low voltage supply option
ION7550/7650 20-60 V DC
PM8000 series20-60 V DC ±10 %
ION8650/8600Auxiliary DC low voltage supply 80-160 V DC ±20 % only
ION620020-60 V DC
CM4000 seriesNo DC low voltage supply option
PM5000 seriesNo DC low voltage supply option
PM800No DC low voltage supply option
ION7400No DC low voltage supply option
ION770020-60 V DC