Reading Power Factor on a CM4000
Issue
User needs to read the power factor value from a CM4000
Product Line
CM4000
Environment
Modbus
Resolution
Steps to convert the PF reading from hexadecimal to decimal value are below:
b. If the sign bit is one (1), the resulting Power Factor is negative (sign multiplier = -1)
4. Multiply resulting decimal value by the scaling factor to obtain the power factor magnitude
5. Multiply the power factor magnitude by the sign multiplier
Example:
Hexadecimal reading of 0x83E4 and scaling factor of 0.001
Result PF = -0.996
Released for: Schneider Electric Canada