How can we help you today?

Graphic Display terminal VW3A1111 of Altivar Variable speed drives (ATV6xx/ATV9xx) used for RESET function

The VW3A1111 Graphic Display Terminal can be used to perform a drive RESET on Altivar ATV6xx / ATV9xx drives, regardless of the configured control channel.
However, this functionality must be explicitly enabled in the drive parameters.

Parameter setting
Navigate to:
5.5 Command and Reference → Stop key Enable (PST parameter)

Default value: Yes
Available values:

No
Yes
All


Key configuration

When set to All, the drive reset function via the VW3A1111 terminal is enabled for all control channels
This allows the reset to be executed independently of the active control mode (e.g. terminals, fieldbus, HMI)


Practical implication

Without selecting All, the reset command may be restricted by the active control channel
For maintenance and troubleshooting, setting All ensures that the HMI reset is always available

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings