How can we help you today?

PM5340 restarts automatically when trying to configure Modbus, Ethernet or BACnet through meter HMI

PM5340 meter restarts when trying to configure Modbus, Ethernet or BACnet through the meter HMI.
This is known issue and it is fixed in the firmware V2.1.37.

Use DLF3000 tool to upgrade the firmware and the default IP address of the meter is 85.16 as the first two values of the IP address, then convert the last two hexadecimal values of the MAC address to decimal and use these as the last two values of the IP address.

Ex: MAC address =00:80:67:82:B8:C8
Default IP =85.16.184.200

Refer the KB article FA236782 for the DLF3000 upgrade procedure

Schneider Electric Canada

Attachment(s)
PM5340_V2_1_3_7.zip [498.25 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings