What is the Unity Pro/EcoStruxure Control Expert 'Optimized code' check box used for in Project Settings -> General -> Build Settings?
Issue
Definition of the 'Optimized code' option in Project Settings.
Product line
Unity Pro, Control Expert
Resolution
- On Premium PLCs and on Quantum 140 CPU 6•• PLCs, the bit %S18 is no longer managed for arithmetic operations on EDT (Elementary Data Types) and tables.
- On Quantum 140 CPU 3••/4••/5•• PLCs, the bit %S18 is no longer managed for arithmetic operations on EDT. The bit %S20 is no longer managed for table indexing (the threshold values are still checked).
| Modification: | Online possible |
| Action required: | Build Changes (Offline) |