How do you control the speed of an Altivar 630 or Altivar 930 drive using the local HMI?
Resolution:
To control the motor speed of an Altivar 630 drive from the local HMI, you must change the speed reference source from the factory default (analog input) to the HMI. Follow the steps below from the drive keypad.
Configure Speed Control from the Local HMI
- Enter the Main Menu on the drive.
- Navigate to:
Main Menu → Complete Settings → Command and Reference - Set the following parameters:
- HMI CMD → Set to Bumpless
(Default is Disabled; this prevents sudden speed changes when switching control sources.) - Ref Freq 1 Config → Change from AI1 (factory default) to Ref Freq – Rmt Term
- HMI CMD → Set to Bumpless
Important Additional Setting
- If the Start/Stop command comes from the terminals, but speed control is performed from the HMI, you must change the Control Mode to Separate.
- This allows different sources to be used for command (Run/Stop) and reference (Speed).
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric Canada
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.