What can cause an CbF or circuit breaker error on the ATV630 and ATV930 Process drives?

Issue:
What can cause an CbF or circuit breaker error on the ATV630 and ATV930 Process drives?

Product Line:
Altvar Machines, Altivar Process Drives

Environment:
All models and serial numbers

Cause:
Inop motor circuit breaker
No mains voltage present
When running if the VBUS is less than USFH after the LCT monitor mains time out.
When stopped  if the ULN is greater than 20vac the error will occur after the LCT Mains time out.

Resolution:
Check the mains voltage
Check the main circuit breaker to see if its tripped.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings