What would cause the ATV630 (or ATV930) M/S configured drives (Multidrive) not to start?

Resolution:
In a MultiDrive Master/Slave configuration, all slave drives must receive and maintain a valid run command before a run command is sent to the master drive.
If the master drive receives a run command before all slave drives have an active run command, the MultiDrive system will not start.


To resolve this issue:

  1. Verify that every slave drive has an active run command.
  2. Confirm the run commands are present on all slave drives before issuing the run command to the master drive.
  3. Reissue the run command to the master drive after all slave drives are ready.

Following the correct run command sequence ensures proper startup of the MultiDrive system.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings