How can the ATV212 be programmed for forced local?

Resolution:

The ATV212 supports Forced Local Mode, which can be activated using either of the following methods:

  1. Permanent Forced Local Mode

    • Set parameter F108 (Always Active Logic) to 48.
    • This configuration keeps Forced Local Mode continuously active.
  2. Forced Local Mode via RES Terminal

    • Set parameter F113 (RES Terminal Function) to 48.
    • Forced Local Mode will be activated whenever the RES terminal is energized or active.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings