EBO SNVT types of third party devices doesnt match with SNVT types in TAC Vsta

EBO system processes data from third-party LonWorks devices according to the definition by Device Template, which is imported to a Building Operation Server (ES/AS-P).

In case SNVT types visible in EBO don't match with SNVTs in the TAC Vista database after the conversion procedure is done, there must be a discrepancy in XIF files that have been imported in advance.

Check the Network Variable index numbers for particular SNVTs that do not match after conversion against XIF files.

Make XIF file correction manually, following the LonMark org Technical Resource guide
chrome-extension://efaidnbmnnnibpcajpcglclefindmkaj/https://www.lonmark.org/wp-content/uploads/2020/12/LmXif4501.pdf

Schneider Electric Canada

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings