What is the input voltage range for the BMXDAI1604?
Issue
The module is specified as 100... 120VAC, is that the absolute full range?
Product line
Modicon X80 IO
Resolution
The specified sensor operating range for the BMXDAI1604 module is 85... 132V.
The input ON is at >= 74V, 2.5MA
The input OFF is at <= 20V, 1mA
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
The module is specified as 100... 120VAC, is that the absolute full range?
Product line
Modicon X80 IO
Resolution
The specified sensor operating range for the BMXDAI1604 module is 85... 132V.
The input ON is at >= 74V, 2.5MA
The input OFF is at <= 20V, 1mA
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)