Issue
The web browsers are reporting that they are unable to connect to the assigned IP addresses even though Unity/Control Expert can connect.
Product line
Unity Pro, Control Expert, Modicon M580, X80 Modules
Resolution
The most common issue is that HTTP needs to be enabled, by default it is disabled in the modules security tab.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
The web browsers are reporting that they are unable to connect to the assigned IP addresses even though Unity/Control Expert can connect.
Product line
Unity Pro, Control Expert, Modicon M580, X80 Modules
Resolution
The most common issue is that HTTP needs to be enabled, by default it is disabled in the modules security tab.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric Canada




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and en expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.