How Do You Configure 2-Wire Control for Level Operation on Altivar Process Drives?
Resolution:
To configure 2-wire control for level operation:
- Go to Main Menu.
- Select Complete Settings.
- Select Command and Reference.
- Set 2-Wire Type to Level (LEL).
With Level (LEL) selected, the drive uses the maintained state of the assigned Run command for 2-wire control.
For additional programming information, refer to the ATV600 Programming Manual.