What Does the INFP/INF25 (Internal Error 25) Mean on Altivar Process Drives?
Resolution:
To troubleshoot the inFP Internal Error 25, follow these steps:
-
Cycle power to the drive.
- Remove line power from the drive.
- Wait until the display is completely off before restoring power.
-
If the error persists, update the drive firmware package to ensure compatibility between the control board hardware and firmware.
If the error remains after completing these steps, contact Schneider Electric Technical Support for further assistance.