ATV320 How do you change the R2 relay to a Normally Closed contact

Issue:
ATV320  How many relay contacts?

Product Line:
Altivar Machine, ATV320

Environment:
All serial numbers

Resolution:
There are 2 sets of  contacts.

R2A - R2C  normally open
NO contact of programmable relay R2

R1A  1 normally open 1 normally closed
R1A NO contact of relay R1
R1B NC contact of relay R1
R1C Common point contact of relay R1