How can we help you today?

Word order for RealFLO Modbus Registers in an x70 Controller

RealFLO Modbus registers require a word order of “High byte/High word first”.  When running a RealFLO flow computer in a SCADAPack x70 controller, the user must ensure that this is set correctly.
The following screen shots (from Remote Connect) show the proper settings for setting the RealFLO Modbus Registers word order.

1. Ensure that the ‘Realflo Flow Computer’ box is checked in the ‘Project Settings’ dialog








2. Ensure that the word order is set properly in the Modbus | Master/Client | FlowComputer dialog.  The correct setting is 'High byte/High word first'.








3. Ensure the word order is set properly in the Modus | SlaveServer dialog.  The correct setting is 'High byte/High word first'.









With the above settings in place, the modbus registers that contain the flow computer data will display the data correctly.

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings