What would cause the ATV320 drives to trip on OSF faults on powerup?
Issue:
The ATV320 drives to trip on OSF faults on powerup?
Resolution:
To clear the OSF fault on powerup:
Set UrES [Mains voltage] to correct value of the line supply voltage.
Parameters described can be accessed by:
DRI- > CONF > FULL > FLT- > CLL
USb- [UNDERVOLTAGE MGT] > enter
UrES [Mains voltage] > enter
Enter the correct line voltage
If set to 380V change to 460V (or appropriate voltage per your application)