How to monitor the SCADAPack x70 time using Modbus.

  • Under the Configuration -SPx70 Controller in RemoteConnect select the object tab.
  • To add the Hour, Minutes and Seconds in the RemoteConnect Object.
  • In Object  Configuration, click add object and enter the following information below when monitoring the HOUR.
  • Assigning modbus register for the HOUR by selecting the modbus tab.
  • click add object and enter the following information below when monitoring the MINUTE.
  • Assigning modbus register for MINUTE by selecting the modbus tab.
  • click add object and enter the following information below when monitoring the SECOND.
  • Assigning modbus register for SECOND by selecting the modbus tab.
  • Hit Apply button then Write the program into the SCADAPackx70 to make changes.
  • Monitor the modbus registers assigned. In this example monitor register 40100 for HOUR, 40101 for MINUTE and 40102 for SECOND.


Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings