What does suffix ET3 indicate on an SEF/SED breaker?
Product Line:
Circuit Breakers
Resolution:
This suffix indicates a 48 Vdc spring charging motor, a 48 Vdc shunt close, a 48 Vdc shunt trip, and a 120 Vac undervoltage trip.