How can we help you today?

Can the trip unit be replaced on electronic trip breaker with a Micrologic Series B trip unit?

Issue:
Series B Micrologic trip unit on older breaker needs to be replaced.

Product Line:
Legacy Series Electronic Trip breakers with Series B Micrologic trip units.

Resolution:
Series B Micrologic trip units installed in the legacy L, M, N, and P breakers are not replaceable. Only Series B trip units installed in SEF/D breakers can be replaced. Series B trip units CANNOT be installed to replace older trip unit series in SEF/D breakers. All of these breakers are now obsolete and need to be replaced with PowerPact or MasterPact electronic trip breakers.

Schneider Electric Canada

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings