How are the long time, short time, instantaneous, and ground fault pickup levels determined on a Micrologic trip unit?

Issue:
How to set dials on trip unit? What do the dials mean?

Product Line:
Circuit Breakers

Resolution:
The settings are determined by a coordination study.

Description of what the dial settings mean:

The long time (current rating) (Ir) is the long time pickup setting multiplied by the sensor plug amperage (In).
The short time current (Isd) equals the short time pickup setting multiplied by the long time pickup setting (Ir).
The instantaneous current pickup amperage (Ii) is equal to the instantaneous pickup setting multiplied by the sensor plug amperage (In).
Ground fault pickup values (Ig) is equal to the ground fault pickup setting multiplied by the sensor plug amperage (In).

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and en expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Center

Help Center

Find support resources for all your needs, in one place.

  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings