How can we help you today?

Can a key interlock be used on an I-line panel with a vertically mounted main breaker?

Issue:
Do we have an interlock for I-line vertically mounted main breakers and a branch breaker?

Product line:
Panelboards

Environment:
Vertically mounted main breakers in I-line panelboards

Resolution:
No.  All I-Line key interlocked breakers must be located in the branch portion of the I-line panel between a backfed main and a branch breaker.  A special mounting bracket is used to mount the interlock.  There isn`t a location for this bracket with a vertically mounted main breaker application.

Schneider Electric Canada

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Help and Contact Center
  • Contact Sales
  • Find our Offices
  • Where to Buy
  • Careers
  • Company Profile
  • Investors
  • Newsroom
  • Report a Misconduct
  • Product Documentation
  • Product Selectors
  • Software and Firmware
  • Product Substitution and Replacement
  • Blog
  • Events
  • Schneider Electric Community
  • Sustainability
  • Legal Information
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings