Issue:
What conductor size are the standard mechanical incoming lugs rated for on an HCM3273-4?
Product Line:
Panelboard
Environment:
ILine Panelboard
Resolution:
The standard aluminum mechanical lug is capable of accepting (2) #4-600kcmil aluminum or copper conductors per phase and neutral.
What conductor size are the standard mechanical incoming lugs rated for on an HCM3273-4?
Product Line:
Panelboard
Environment:
ILine Panelboard
Resolution:
The standard aluminum mechanical lug is capable of accepting (2) #4-600kcmil aluminum or copper conductors per phase and neutral.
Released for: Schneider Electric Canada