Can you get a 400A LC main breaker, 42 circuit, NF panelboard with 42,000 AIC rating in a NEMA 3R enclosure?
Issue:
Is there a NEMA 3R Enclosure for an LC main breaker 400Amps for an NF Panelboard?
Product Line:
Panelboards
Environment:
NF Panelboards
Resolution:
400A main breaker NF panel, 42 circuits, with a 42,000 AIC rating in a NEMA 3R enclosure is not available because the main breaker is an LC frame and it must go into a 26`` wide box 8`` deep. We do not have a NEMA 3R box that will fit.
Is there a NEMA 3R Enclosure for an LC main breaker 400Amps for an NF Panelboard?
Product Line:
Panelboards
Environment:
NF Panelboards
Resolution:
400A main breaker NF panel, 42 circuits, with a 42,000 AIC rating in a NEMA 3R enclosure is not available because the main breaker is an LC frame and it must go into a 26`` wide box 8`` deep. We do not have a NEMA 3R box that will fit.